What Size Ground Rod For 100 Amp Service
-
What size footing wire for 100-amp sub-panel?
I but dug an 18" deep trench from the house to my detached garage and I'one thousand well-nigh to run 3-guess service cable for my new 100-amp sub panel. The garage is simply x feet away from the house. The cablevision will exist encased in PVC conduit. The main 200-amp service console at the house is well-grounded, and a couple of electricians here in LA take told me that I don't demand any additional grounding rods for the sub-console, merely a dark-green grounding wire that will become run back to the main service console.
Anybody know what size wire I need for the green ground wire? I recollect I read 8 someplace, only I want to exist sure.
Cheers!
- Jason
-
-
100 amp feeder (al) is 2-two-four-half-dozen
-
Jason, I would suggest y'all get to know your local inspector and ask him what he wants to meet. Municipalities don't HAVE to follow the NEC, or even the latest NEC, but every bit far every bit I know, the NEC a basis rod (sometimes 2 ground rods) is required for discrete structures.
-
Originally Posted past John Coloccia
A jurisdiction may have stricter regs, simply may non have lesser requirements, so the above quote does not apply in the Country of California.
-
For a excursion protected by a 100 A breaker, the minimum ground wire size is #8 copper or #6 aluminum.
-
Jason, A separate edifice always requires a grounding electrode arrangement in addition to the equipment grounding conductor that you mention. The only exception is if the dissever building is fed with just a single branch circuit (2014 NEC 250.32a). If you are using rod type electrodes, you actually need to drive two of them, at a minimum of 6' apart. The simply way that you tin can go by with a single ane, is if you can bear witness by measurement that the ground resistance is 25 ohms or less. The measurement must be performed with a dedicated ground resistance meter, something that very few contractors have. Information technology is almost always easier and more cost constructive to satisfy the NEC requirement past supplementing i ground rod with an boosted 1 (250.53(a)(two). Although the minimum size grounding electrode usher is typically #viii copper for a 100 amp service (it'southward actually determined past feeder size, not amperage), the NEC requires that conductors smaller than #half-dozen be physically protected (usually conduit). If you lot run a #6 bare copper GEC, you tin can run it exposed on the surface unless it is field of study to severe physical damage (250.64(B).
Concluding edited by Matt Marsh; x-02-2014 at ii:37 PM.
-
Thanks for the advice, guys! Only to exist safe, I went ahead and installed 2 copper ground rods and continued with #6 bare copper (sleeved in PVC conduit until is disappears below ground). I besides used a #6 THWN green ground wire to connect back to the master service console. Grounds and neutrals in the sub panel are separated.
Originally Posted past Matt Marsh
-
Originally Posted past Mark Bolton
-
I used #2 copper for both hots and neutral and #6 copper for the grounds.
Originally Posted past Rollie Meyers
-
Here you could not become a pass on installing electrical wire eighteen" deep unless the circuit handles 20 amps or less. Hither they mandate the NEC 30" only as if it'southward a commercial burial. Information technology wouldn't affair if it was encased in conduit or not. Regarding the size of the grounding wire, I prefer to go one size larger than mandated for the grounding wire. In that location will also be a directive on the minimal length of the grounding wire. NEC is 8' minimal depth if retentiveness serves correctly. Not certain of California code, but they typically meet or exceed the codes of the NEC.
-
Originally Posted by Rich Riddle
Last edited by Rollie Meyers; ten-13-2014 at ix:31 PM.
-
I actually dug the trench closer to 20 inches so that I accept at to the lowest degree eighteen inches of make full on top of the conduit ane-1/two" conduit.
Originally Posted by Rollie Meyers
What Size Ground Rod For 100 Amp Service,
Source: https://sawmillcreek.org/showthread.php?222258-What-size-ground-wire-for-100-amp-sub-panel
Posted by: hodgsonthille.blogspot.com
0 Response to "What Size Ground Rod For 100 Amp Service"
Post a Comment